Fluke 772 Milliamp Clamp Meters

Are you spending time:

  • Taking mA measurements by removing a wire and breaking the loop
  • Calling the control room to isolate a loop
  • Testing analog input/output on a console
  • Troubleshooting devices with mA inputs and outputs
  • Repairing intermittent or erratic 4-20 mA loops
  • Going back to the shop to get extra tools

If you need more time in your busy day take a good look at the Fluke 772 mA Clamp Meters. It’s designed to save you time, and money, by eliminating time wasting activities. Now you can troubleshoot and repair 4-20 mA loops without breaking the loop or bringing down the system.



Description

Specifications

Diameter of measurable conductor 0.177 or 4.5 mm max
Operating temperature -10 to 50 ºC
Storage Temperature -25 to 60ºC
Operating Humidity < 90% @ <30 ºC, < 75% @ 30 to 55ºC
Operating Altitude 0 to 2000 m
IP Rating IP 40
Size 59 x 38 x 212 mm, (2.32 x 1.5 x 8.35 in.)
Weight 260G, (9.1 oz.)
Vibration Random 2 g, 5 to 500 Hz
Shock 1 meter drop test (except the jaw)
EMI/RFI Meets EN61326-1
Note: For current measurement w/ JAW, add 1mA to
specification for EMC field strengths of 1V/m up to 3V/m.
Temperature Coefficient 0.01% ºC
(<18? or > 28?)
Power, battery life (2) AA 1.5 V Alkaline, IEC LR6, 40 hours typical
Warranty Three years for electronics one year for cable and clamp assembly

 

Functional Specifications

mA measurement
(Measured by clamp)
Resolution and Range:     0 to 20.99 mA
Accuracy:                        0.2% + 5 counts
Resolution and Range:     21.0mA to 100.0 mA
Accuracy:                        1% + 5 counts
mA measurement
(Measured in series with test jacks)
Resolution and Range:
Resolution and Range:     0 to 24.00 mA
Accuracy:                        0.2% + 2 counts
mA source (Maximum mA Drive:
24 mA into 1,000 ohms)
Resolution and Range:
Resolution and Range:     0 to 24.00 mA
Accuracy:                   0.2% + 2 counts
mA simulate
(Maximum voltage 50 V dc)
Resolution and Range:
Resolution and Range:     0 to 24.00 mA
Accuracy:                   0.2% + 2 counts
Fluke 772 Milliamp Clamp Meters